CFM Calculator

How much airflow does this room or space need? Get the CFM right and the duct sizing, equipment selection, and comfort all follow.

Calculation Method

Choose how you want to calculate. Volume + Air Changes is the standard method for room-level airflow. BTU + Temperature works backward from a known load. Tonnage gives a quick system-level estimate.

Room Details

sq ft
Floor area of the room or space.
ft
Standard residential is 8 ft. Vaulted or commercial may be 10–20 ft.
Sets the default air changes per hour (ACH) — how many times the room's air volume is fully replaced in one hour. Higher ACH = more ventilation needed.
Auto-set by room type above. Override if you have a specific requirement.

BTU Method (Alternative)

BTU/hr
Total cooling or heating load for the space. Use this method if you already know the load from a Manual J or equipment spec.
°F
Difference between supply air and return air temperature. Standard cooling is 18–22°F. Standard heating is 25–35°F.

Tonnage Method (Quick Estimate)

tons
1 ton = 12,000 BTU/hr of cooling capacity.
Standard is 400. Humid climates like FL trend toward 350. Dry climates toward 450.

Enter room dimensions or BTU load to calculate required airflow.

What to do with this number
  1. Size your ductwork. Use the CFM result to determine duct diameter. The Duct Sizing Calculator takes this number as its primary input.
  2. Verify against equipment specs. Your system's total CFM should match the air handler or furnace rating. If room-level CFMs add up to more than the system delivers, some rooms will be starved.
  3. Treat the ACH as a starting point. The room type sets a recommended air change rate, but your specific conditions may need adjustment. High heat loads, unusual occupancy, or poor insulation can push the requirement higher.
  4. Consult Manual D for permit work. This calculator gives planning estimates. Permitted installations require a formal Manual D duct design showing friction rates, fittings, and system balance.

These calculations use ASHRAE Fundamentals and ACCA recommended air change rates. They are estimates for planning. Verify with Manual D duct design for permit-required work.